Products > Cables > Instrumentation Cables > RE-2Y(St)Y-fl-TIMF

RE-2Y(St)Y-fl-TIMF

FeatureDescription
StandardEN 50288-7
ConductorStranded bare copper wire, Class 2 (IEC 60228)
InsulationPolyethylene (PE) compound
Core IdentificationBlack, white, and red cores numbered according to EN 50288-7
Triple FormationThree conductors twisted into a triple
Individual ScreeningAluminum/polyester tape over tinned copper drain wire for each triple
Overall ScreeningAluminum/polyester tape over tinned copper drain wire
Outer SheathPVC compound, flame retardant (TM1)
Sheath ColourRAL 9005 (black) or RAL 5015 (blue)
Rated Voltage (U₀/U)500 V
Test VoltageCore-Core: 2000 V AC; Core-Screen: 2000 V AC
Insulation Resistance≥ 5000 MΩ·km at 20°C
Mutual CapacitanceMax. 100 pF/m (1 kHz)
Temperature RangeOperation: -30°C to +70°C; Installation: -5°C to +50°C
Minimum Bending Radius7.5 × outer diameter
Flame RetardanceIEC 60332-1 & EN 50266-2-4
ApplicationsUsed for transmission of analogue and digital signals in instrument and control systems at chemical and petrochemical plants, power plants, natural gas and petroleum facilities. Not suitable for direct connection to low impedance sources or direct burial. Suitable for indoor and outdoor installations, in dry and wet locations; on racks, trays, and in conduits.
Privacy policy